Technical Data - AEG Protect C.R Operating Instructions Manual

Table of Contents

Advertisement

3.4

Technical Data

Type power
PROTECT C. 1000 R (S)
PROTECT C. 2000 R (S)
PROTECT C. 3000 R (S)
PROTECT C. 6000 R
UPS Input
Rated input voltage
Voltage tolerance range
C. 1000 R (S) – C. 3000 R (S) 160 Vac – 300 Vac ± 5 Vac
C. 6000 R
Nominal frequency
Frequency tolerance range
Curr. consumption (full load)
PROTECT C. 1000 R (S)
PROTECT C. 2000 R
PROTECT C. 2000 R S
PROTECT C. 3000 R (S)
PROTECT C. 6000 R
Input power factor
C. 1000 R (S) – C. 3000 R (S)
C. 6000 R
Connection
C. 1000 R (S) – C. 3000 R (S)
C. 6000 R
1000 VA (cos  = 0.7 lag.)
700 W
2000 VA (cos  = 0.7 lag.)
1400 W
3000 VA (cos  = 0.7 lag.)
2100 W
6000 VA (cos  = 0.7 lag.)
4200 W
220 / 230 / 240 Vac
Bypass 80 Vac – 264 Vac
176 Vac – 276 Vac ± 3 %
Bypass 176 Vac – 261 %
50 Hz / 60 Hz
(automatic detection)
± 4 Hz
7 A
10 A
12 A
16 A
31 A
≥ 0.96
≥ 0.98
non-heating
appliance connector
Terminal block
15