Refrigeratin Gcycle Diagram - Toshiba Carrier MMU-AP0182H2UL Service Manual

Split type
Hide thumbs Also See for Carrier MMU-AP0182H2UL:
Table of Contents

Advertisement

Liquid side
Gas side
Strainer
Pulse Motor
Valve (PMV)
Sensor
(TC2)
Functional part name
Pulse Motor Valve
Temp. sensor
5. REFRIGERATING CYCLE DIAGRAM
Capillary tube
Strainer
Sensor
(TCJ)
PMV
(Connector CN082 (6P): Blue)
1) Controls super heat in cooling operation
2) Controls under cool in heating operation
3) Recovers refrigerant oil in cooling operation
4) Recovers refrigerant oil in heating operation
1. TA
(Connector CN104 (2P): MMU, MMC: Yellow, MMK: White)
1) Detects indoor suction temperature
2. TC1
(Connector CN100 (3P): Brown)
1) Controls PMV super heat in cooling operation
3. TC2
(Connector CN101 (2P): MMU, MMC: Black, MMK: Blue)
1) Controls PMV under cool in heating operation
4. TCJ
(Connector CN102 (2P): MMU, MMC: Red, MMK: Yellow)
1) Controls PMV super heat in cooling operation
Air heat exchanger
at indoor side
Fan
Sensor
M
(TA)
Functional outline
27
Sensor
(TC1)
Fan motor

Advertisement

Table of Contents
loading

Table of Contents