AU48NFIBIA PCB ports name and functions

Ports
R, S, T
Power supply ports
U, V, W
Compressor ports
E
Grounded port
N
Neutral wire port
L1, L2
Reactance port
CN102
Current transducer port
CN211, CN212
Fan motor port
CN205
Water pump port
CN206
Electric heater port
CN207
Solenoid valve port
CN208
Solenoid valve port
CN209
Four-way valve port
CN210
Oxygen generator port
CN303
Testing board port
CN304
Communication port
Fan motor port for dispersing
CN307, CN308
heat
CN310
EEV port
CN311
Radiator temp. sensor port
Mid-condenser
CN312
port
CN313
Defrosting temp. sensor port
CN314
Ambient temp. sensor port
CN315
Suction temp. sensor port
CN316
Discharging temp. sensor port
CN317
Low pressure switch port
CN318
High pressure switch port
Ports name
temp.
sensor
-148-
>a__WcU[S^ <[c >a`V[e[a`Wc
Wiring method
To power of 3 PH, 380V, 50Hz
To motor (pay attention to phase sequence)
Grounding (less than 10Ω;more thanφ1.6mm)
If 3 phase, it is connected to neutral wire; if 1
phase, it is blank.
To wire of reactance (non-polar)
To current transducer
To fan motor
To water pump (be spare)
To electric heater
To solenoid valve
To solenoid valve
To four-way valve
To oxygen generator (blank temporarily)
To testing board. Used to modify, check data for
after sale personnel.
To C1, C2 of communication block
To fan motor for dispersing heat (be spare)
To outdoor electronic expansion valve
To radiator temp. sensor (blank temporarily)
To mid-condenser temp. sensor
To defrosting temp. sensor
To ambient temp. sensor
To compressor suction temp. sensor
To discharging temp. sensor
To low pressure switch
To high pressure switch