7.1.5 Combination example:

8 by 1:
Haier
NOTE:
1.When AU48 unit is connected with 8 indoor units, pay attention that the total capacity of indoor
units must not exceed 130% of outdoor cooling capacity.
2.Wall-mounted type can not be connected with 8 units by the outdoor unit. But you can refer to
the above combination example.
3.when outdoor unit connects with 8 colorful screen wall-mounted units, please set address by
dialing switch. When you connect old wall type units, you only can connect max 6 sets, and set
their addresses with address setting controller.
4.when outdoor unit connects with 8 units according to <admissible combination
example>(except for the No.3 example), please set address of the anterior 6 indoor units with
the address-setting remote controller, and then set address of the latter 2 indoor units with
dialing switches.
Or using below method to set unit 7 and 8:
seconds press button 1, then loosen them simultaneously. The LCD will display "7", which
stands for selecting unit 7. And then press button "set", you can set unit 7.
By the same method, press button 6 plus button 2, you can set unit 8.
>a__WcU[S^ <[c >a`V[e[a`Wc
MP2
Press button 6 and at the same time in 2
-58-
AS06
AS06
electronic expansion valve
AS06
AS06
AS06
AS06
AE07
AE07