Easy Series (ICP-EZM2) | Installer Guide | 2.0 Installation
2.4

DX2010 Installation (Step 4)

The control panel supports up to three DX2010 Input Expanders for Points 9 to 32.
Refer to the DX2010 Installation Instructions (P/N: 49533) for more information.
1. Mount the DX2010 into the
control panel's enclosure, or other
suitable enclosure.
2. Set the DX2010's DIP switches.
-
Points 9 to 16 = Address 102
-
Points 17 to 24 = Address 103
Points 25 to 32 = Address 104
-
3. Connect the DX2010 to the
control panel.
Connect a wire jumper to the
TMPR and COM terminals to
disable the DX2010's tamper
input.
For point wiring options, refer to
Section 2.6 Supervised Point
Connections on page 14.
12
102
103
OFF
104
+OUT-
TMPR
R
B
G
Y
1 COM
G
B
R
Bosch Security Systems, Inc. | 5/07 | F01U025147-01
=
ON
Y