Panasonic KT2 Instruction Manual page 10

Hide thumbs Also See for KT2:
Table of Contents

Advertisement

Decimal point place selection
• Selects decimal point place.
• Available only for DC input
: No decimal point
: 1 digit after decimal point
: 2 digits after decimal point
: 3 digits after decimal point
PV filter time constant setting
• Sets PV filter time constant.
Input fluctuation due to the noise can be reduced.
If the value is set too large, it affects control result due to the
delay of response.
• Setting range: 0.0 to 10.0 seconds
OUT1 (Heating) high limit setting
• Sets OUT1 (Heating) high limit value.
Not available if OUT1 (Heating) is ON/OFF action
• If Heating/Cooling control option is added, OUT1 terminals are
used for Heating output terminals.
• Setting range: OUT1 (Heating) low limit value to 105%
(Setting higher than 100% is effective to DC current output type)
OUT1 (Heating) low limit setting
• Sets OUT1 (Heating) low limit value.
Not available if OUT1 (Heating) is ON/OFF action
• If Heating/Cooling control option is added, OUT1 terminals are
used for Heating output terminals.
• Setting range: –5% to OUT1 (Heating) high limit value
(Setting less than 0% is effective to DC current output type)
OUT1 (Heating) ON/OFF action hysteresis setting
• Sets ON/OFF action hysteresis for OUT1 (Heating).
• Available only when OUT1 (Heating) is ON/OFF action
• Setting range: 0.1 to 100.0
EV1 output selection
• Selects a function for EV1 output terminals.
• Not available if Heating/Cooling control option is added, since
EV1 terminals are used for Cooling output terminals.
: A1 output
: A2 output
: Common to A1 and A2 output
EV2 output selection
• Selects a function for EV2 output terminals.
• Not available if Serial communication option is added
: A1 output
: A2 output
: Common to A1 and A2 output
Overlap band/Dead band setting
• Sets the overlap band or dead band for OUT1 (Heating side) and
OUT2 (Cooling side).
+ set value: Dead band
– set value: Overlap band
• Available only when the Heating/Cooling control option is added
• Setting range: –100.0 to 100.0
OUT2 (Cooling) ON/OFF action hysteresis setting
• Sets ON/OFF action hysteresis for OUT2 (Cooling side).
• Available only when the Heating/Cooling control option is added
• Setting range: 0.1 to 100.0
10
No decimal point
0.0 seconds
100%
0%
1.0
( ), or 1 to 1000
A1 output
A2 output
0.0
( ), or 1 to 1000
1.0
( ), or 1 to 1000