A1 type selection
• Selects an A1 (Alarm 1) type.
:
No alarm action
:
High limit alarm
:
Low limit alarm
:
High/Low limits alarm
:
High/Low limit range alarm
:
Process high alarm
:
Process low alarm
:
High limit alarm with standby
:
Low limit alarm with standby
:
High/Low limits alarm with standby
: Timer function
: Pattern end output
If Timer function is selected, Timer function works only
when Delay action type, Delay time and DI (digital input)
function are set or selected.
A2 type selection
• Selects an A2 (Alarm 2) type.
• Alarm type selection and default value are the same as those of
A1 type selection.
A1 hysteresis setting
• Sets hysteresis for A1.
• Not available if No alarm action, Timer function or Pattern end
output is selected during A1 type selection
• Setting range: 0.1 to 100.0 ( ), or 1 to 1000
A2 hysteresis setting
• Sets hysteresis for A2.
• Not available if No alarm action, Timer function or Pattern end
output is selected during A2 type selection
• Setting range: 0.1 to 100.0 ( ), or 1 to 1000
A1 action delayed timer setting
• Sets action delayed timer for A1.
When setting time has elapsed after the input enters the alarm
output range, the alarm is activated.
• Not available if No alarm action, Timer function or Pattern end
output is selected during A1 type selection
• Setting range: 0 to 9999 seconds
A2 action delayed timer setting
• Sets action delayed timer for A2.
When setting time has elapsed after the input enters the alarm
output range, the alarm is activated.
• Not available if No alarm action, Timer function or Pattern end
output is selected during A2 type selection
• Setting range: 0 to 9999 seconds
Alarm HOLD function selection
• Selects whether alarm HOLD function for A1 or A2 is used or
not used.
• This setting item is common to A1 and A2.
Not available if No alarm action, Timer function or Pattern end
output is selected during A1 or A2 type selection.
: Alarm Not Holding
: Alarm Holding
11
No alarm action
No alarm action
1.0
1.0
0 seconds
0 seconds
Alarm Not Holding