Panasonic KT2 Instruction Manual page 9

Hide thumbs Also See for KT2:
Table of Contents

Advertisement

Display used for explaining setting items
Setting items (Section "5.2 Initial setting" and setting modes from Section 6.1 to 6.3) are explained as follows.
(e.g.) Input type selection
Auxiliary function setting mode 2
Display
means that input type characters
value
(K –200 to 1370 ) are indicated in turn.
Item, Function, Setting range
Input type selection
• The input type can be selected from thermocouple (10 types),
RTD (2 types), DC current (2 types) and DC voltage (4 types).
The unit
/
can be selected as well.
• When changing the input from DC voltage to other inputs,
remove the sensor connected to this controller first, then
change input type. If the input is changed with the
sensor connected, the input circuit may break.
:
K
:
:
J
:
R
:
S
:
B
:
E
:
T
:
N
:
PL-
:
C (W/Re5-26)
:
Pt100
:
JPt100
:
Pt100
:
JPt100
:
K
:
:
J
:
R
:
S
:
B
:
E
:
T
:
N
:
PL-
:
C (W/Re5-26)
:
Pt100
:
JPt100
:
Pt100
:
JPt100
:
4 to 20mA DC
:
0 to 20mA DC
:
0 to 1V DC
:
0 to 5V DC
:
1 to 5V DC
:
0 to 10V DC
Scaling high limit setting
• Sets scaling high limit value.
• Setting range: Scaling low limit value to input range high
limit value
Scaling low limit setting
• Sets scaling low limit value.
• Setting range: Input range low limit value to scaling high limit
value
9
and selected
Default value
K
(-200 to 1370 )
-200 to 1370
-199.9 to 400.0
-200 to 1000
0 to 1760
0 to 1760
0 to 1820
-200 to 800
-199.9 to 400.0
-200 to 1300
0 to 1390
0 to 2315
-199.9 to 850.0
-199.9 to 500.0
-200 to 850
-200 to 500
-320 to 2500
-199.9 to 750.0
-320 to 1800
0 to 3200
0 to 3200
0 to 3300
-320 to 1500
-199.9 to 750.0
-320 to 2300
0 to 2500
0 to 4200
-199.9 to 999.9
-199.9 to 900.0
-300 to 1500
-300 to 900
-1999 to 9999
-1999 to 9999
-1999 to 9999
-1999 to 9999
-1999 to 9999
-1999 to 9999
1370
-200