KNX Technical Reference Manual
®
ABB-i-Bus
-KNX Millenium
Note
The following parameters are available only when parameter "Control type heating" is set on "PI
continuous", "PI PWM (1-bit)" or on "FanCoil".
General parameters for "Control
function = Heating"
Status object heating
Control type heating
Mode of the control value for heating
Hysteresis heating (1/10 K)
cyclical sending of the control value heating
(min)
Additional parameters for "Control
function = Heating"
Control parameter
Type of heating system
P amount heating (1/10 K)
I-component heating (min.)
max. control value heating
min. control value heating
KNX Technical Reference Manual | 1473-1-7819
Settings
• deactivated
• activated
• 2-point 1-bit (Off/On)
• 2-point 1-byte (0/100%)
• PI continuous
• PI PWM (1-bit)
• FanCoil
• Normal
• inverse
3 ... 255
1 ... 60
Settings
• via system type
• Free paramaterization
For "PI continuous"
• Hot-water heating
and "PI PWM (1-bit)"
• Electric heating
(1.5 K/50 min)
• Floor heating (4
K/200 min)
For "FanCoil"
FanCoil (4 K/90 min)
10 ... 100
0 ... 255
0 ... 255
0 ... 255
Description of applications /
Comments
Only available when parameter "„Control
type heating" is set on "2-point 1-bit
(Off/On)" or "2-point 1-byte (0/100%)".
Comments
Only available when parameter "Control
parameter" is set on "Free
paramaterization".
objects
— 32 —