ABB -i-Bus-KNX Millenium Technical Reference Manual page 38

Room temperature controller
Hide thumbs Also See for ABB-i-Bus-KNX Millenium:
Table of Contents

Advertisement

KNX Technical Reference Manual
®
ABB-i-Bus
-KNX Millenium
Note
The following parameters are available only when parameter "Control type cooling" is set on "PI
continuous", "PI PWM (1-bit)" or on "FanCoil".
General parameters for "Control
function = Cooling"
Status object cooling
Control type cooling
Mode of the control value for cooling
Hysteresis cooling (1/10 K)
cyclical sending of the control value cooling
(min)
Additional parameters for "Control
function = Cooling"
Control parameter
Type of cooling system
P amount cooling (1/10 K)
I-component cooling (min.)
max. control value cooling
min. control value cooling
KNX Technical Reference Manual | 1473-1-7819
Settings
• deactivated
• activated
• 2-point 1-bit (Off/On)
• 2-point 1-byte (0/100%)
• PI continuous
• PI PWM (1-bit)
• FanCoil
• Normal
• inverse
3 ... 255
1 ... 60
Settings
• via system type
• Free paramaterization
Für „PI continuous"
Cooling ceiling (
und „PI PWM (1-bit)"
Für „FanCoil"
FanCoil (4 K/90 min)
10 ... 100
0 ... 255
0 ... 255
0 ... 255
Description of applications /
Comments
Only available when parameter "„Control
type cooling" is set on "2-point 1-bit
(Off/On)" or "2-point 1-byte (0/100%)".
Comments
Only available when parameter "Control
parameter" is set on "Free
paramaterization".
objects
— 38 —