[VI
Refrigerant Circuit]
3.
Be
control/er
(1) G type
Part name
Symbols
Part
Usage
Specifications
Check method
(functions)
code
Pressure
PS1
1) Detects high pressure
Pressure
sensor
(High pres-
2) LEV control
PS1
Q-.4.15
MPa
(601
psi)
sure side)
VouIO.S-3.5V
123
0.071V10.098
MPa
/14psi)
/
Con-
Pressure (MPal
PS3
1) Detects intermediate
nector
=1.38 x Vou! [V}-O.69
(Intermedi-
Pressure (psi]
pressure
~~.38
x Voul
M -
0.69) x 145
ate pres-
2) LEV control
1 GND
(Black)
sure)
2 Voul (While)
3 Vee (DC5V) (Red)
Thermistor
TH11
LEV control
(Liquid inlet
(Liquid level control)
Ro
=
15k"
lempera-
ROIeo=
3460
ture)
1
1
Rt=
15expl3460
(m+! -
273)}
TH12
LEV control (Superheat)
(Bypass
0°C[32°F] : 15kohm
outlet tem-
1O°C[50°F] :9.7kohm
perature)
20°C[68°F] :6.4kohm
25°C[77°F] :5.3kohm
TH15
LEV control (Superheat)
30°C[86°F] :4.3kohm
(Bypass in-
40°C[1 04
oF]
:3.1 kohm
let tempera-
ture)
TH16
LEV control (Subcool)
(liqUid re-
frigerant
tempera-
ture)
Solenoid
SVM1
Opens during cooling and de- AC208-230V
Continuity
valve
frost modes
Open while being poweredl
check with a
SV.A
closed while not being pow-
tester
Provides refrigerant to indoor
ered
unit in cooling operation
SV.B
Provides refrigerant to indoor
unit in heating operation
SV.C
Provides refrigerant to indoor
unit in cooling operation
LEV
LEV1
1) Liquid level control
DC12V
Same as
2) Pressure differential con- Opening of a valve driven by a
indoor LEV
LEV3
trol
stepping motor
0-2000 pulses
HWE080JA