Switch Settings And Address Settings - Mitsubishi Electric PURY-P72 Service Handbook

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

1---
[II Restrictions)
2) Remote controller wiring
MA remote controller*1
M-NET remote controller*2
Type
VCTF,VCTFK,CVV,CVS,VVR,VVF,VCT Shielded cable MVVS
Number of
2-core cable
2-core cable
cores
Cable type
0.3 to 1.25mm 2 *3
0.3 to 1.25mm 2 *3
Cable size
[AWG22 to 16)
*4
[AWG22 to 16)
*4
(0.75 to 1.25mm 2 )
(0.75 to 1.25mm 2 )
[AWG18 to 16)
[AWG18 to 16)
Maximum overall line
The section of the cable that exceeds 10m
200 m [656ft) max.
[32ft) must be included in the maximum in-
length
door-outdoor transmission line distance.
*1 MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21 MAA), MA simple remote controller, and
wireless remote controller.
*2 M-NET remote controller refers to ME remote controller and ME simple remote controller.
*3 The use of cables that are smaller than 0.75mm 2 [AWG18) is recommended for easy handling.
*4 When connected to the terminal block on the Simple remote controller, use cables that meet the cable size specifi-
cations shown in the parenthesis.
[3] Switch Settings and Address Settings
1.
Switch setting
Refer to section "[5) An Example of a System to which an MA Remote Controller is connected -
[7)
An Example of a System
to which both MA Remote Controller and M-NET Remote Controller are connected" before performing wiring work.
Set the switches while the power is tumed off.
If the switch settings are changed while the unit is being powered, those changes will not take effect, and the unit will not
function properly.
Units on which to set the switches
Symbol
Units to which the power must be shut off
CITY MULTI indoor unit
Main/sub unit
IC
Outdoor units *3 and Indoor units
LOSSNAY, OA processing unit *1
LC
Outdoor units *3 and LOSSNAY
M-NET remote controller
Main/sub remote
RC
Outdoor units *3
controller
MA remote controller
Main/sub remote
MA
Indoor units
controller
CITY MULTI outdoor uni(2
OC,OS
Outdoor units *3
BC controller
Main
BC
Outdoor units *3 and BC controller
Sub1,2
BS1, BS2
Outdoor units *3 and BC controller
*1. Applicable when LOSSNAY units are connected to the indoor-outdoor transmission line.
*2. The outdoor units in the same refrigerant circuit are automatically designated as OC and OS in the order of capacity
from large to small (if two or more units have the same capacity, in the order of address from small to large).
*3. Tum off the power to all the outdoor units in the same refrigerant circuit.
HWE0803A
- 19-
GB