Mitsubishi Electric PURY-P72 Service Handbook page 138

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[VII
Control
1
2) PURY-P96, P120THMU-A
Function according to switch
Switch setting timing
Switch
Function
setting
OFF
ON
OFF
ON
SW1
1
Enabling/disabling the following error
Error detec-
Error detec-
Anytime after power on
detection functions;
tion enabled
tion disable
ACCT/DCCT sensor failure
(No load op-
(5301 Detail No. 115, 116)
eration is pos-
ACCT/DCCT sensor circuit failure
sible.)
(5301 Detail NO.117,118)
IPM open/Disconnected CNCT2
(5301 Detail No. 119)
Detection of erroneous wiring
(5301 Detail No.120)
2
-
-
-
-
-
3
-
-
-
-
-
4
-
-
-
-
-
5
-
-
-
-
-
6
-
-
-
-
-
Note
I
tAli are set to OFF at factory shipment. Unless otherwise specified, set the switch to OFF where indicated by "-." which may
be set to a certain setting for a reason.
-Leave SW1-1 to OFF dUring normal operation. If it is set to ON, errors cannot be detected and the unit may be damaged.
HWE0803A
-128 -