Standard Operation Data (Reference Data) - Mitsubishi Electric PURY-P72 Service Handbook

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[ VIII Test Run Mode]
[7] Standard Operation Data (Reference Data)
1. Single unit
(1) Cooling only operation
Outdoor unit model
Operation
PURY-P72THMU-A
PURY-P96THMU-A
Model name of BC controller
CMB-P104NU-G
CMB-P104NU-G
Indoor
26.rC/19.4°C
26.7°C/19.4°C
Ambient
[80 °F/67 OF]
[80 °F/67 OF]
tempera-
DBIWS
ture
Outdoor
35°C/-
35°C/-
[95°F/-]
[95°F/-]
No. of connected units
3
2
Unit
Indoor unit
No. of units in operation
3
2
Operating
Model
-
24/24/24
48/48
conditions
Main pipe
5 [16-3/8"J
5 [16-3/8"]
Piping
Branch pipe
m
10 [32-3/4"]
10 [32-3/4"]
[ttl
Total pipe length
35 [114-13/16"]
25 [82]
Fan speed
-
Hi
Hi
Amount of refrigerant
kg
19.1
[42]
21.3 [47]
[Ibs-oz]
Electric current
A
15.4
23.2
Outdoor
Voltage
V
230
230
unit
Compressor frequency
Hz
43
65
LEV open-
Indoor unit
180/200/220
387/387
Pulse
ing
se
controller (1/2/3)
2000/-/180
2000/-/170
High pressure(63HS 1)/
2.65/0.90
2.66/0.93
Pressure
Low pressure(63LS)
MPa
[384/130J
[385/134]
BC controller on the liquid side(PS1)/
[psi]
2.59/2.59
2.58/2.58
Intermediate part(PS3)
[375/375]
[374/374]
Discharge (TH4)
76 [169]
85 [185]
Heat exchanger outlet
41
[106]
39 [102]
(TH3)
Outdoor
Accumulator inlet
14 [57]
8 [46J
Temp. of
unit
each sec-
Accumulator outlet
°c
14 [57]
8 [46]
tion
Compressor inlet
[OFJ
23 [73]
19 [66]
Compressor shell bottom
34 [93]
40
[104]
LEV inlet
24 [75]
19 [66]
Indoor unit
Heat exchanger inlet
12 [54]
6 [43]
HWEOB03A
- 163-
GB