Commissioning
6

Additional settings

6.6 Additional settings

6.6.1 Restoring parameters to factory settings

STARTER software
IOP-2
BOP-2

6.6.2 Setting the PID controller

60 | 98
Siemens
Building Technologies
NOTICE
Risk of data loss!
When you reset parameters to the factory settings, all stored parameters and data
will be lost. Once the device has been reset to its factory settings, it must be
commissioned again.
Make a copy of the working settings before you reset the variable speed drive
to its factory settings.
The communication settings and the settings of the motor standard (IEC/NEMA)
are retained after resetting.
Proceed as follows to reset the variable speed drive to its factory settings:
1. Go online with STARTER.
2. Click the
button.
1. Select Options > Parameter settings > Reset drive to factory settings.
2. Confirm with OK.
1. Select Options > DRVRESET in the menu.
2. Confirm with OK.
Setting the PID controller
If the PID controller is activated, the set ramp times are bypassed in p1120 and
p1121 (applies only to FW < V4.7 SP3).
Therefore, define the following settings for smoothing times, ramp times and
controller.
Parameter
Setting
p2200
1
p2253
r2224
p2257
30s *
p2258
30s *
p2264
r755.1
p2265
10s *
Function
Setting of the signal source for switching the technology
controller on/off.
Technology controller setpoint
r755.0: Analog setpoint (AI0)
r2224: Technology controller fixed value
r2050.1: Setpoint fieldbus
Technology controller setpoint ramp-up time
Technology controller setpoint ramp-down time
Technology controller actual value
r755.1: Analog actual value (AI1)
Technology controller actual value filter time constant
A5E36496664A_d
2016-03-17