Siemens G120P Technical Manual page 95

Variable speed drive
Table of Contents

Advertisement

Siemens
Building Technologies
Environmental conditions
Climatic ambient conditions
Storage (in transport packaging) according to
EN 60721-3-1
Transport (in transport packaging) according
to EN 60721-3-2
Operation acc. to EN 60721-3-3
Environmental class/harmful chemical
substances:
Storage (in transport packaging) according to
EN 60721-3-1
Transport (in transport packaging) according
to EN 60721-3-2
Operation acc. to EN 60721-3-3
Organic/biological influences:
Storage (in transport packaging) according to
EN 60721-3-1
Transport (in transport packaging) according
to EN 60721-3-2
Operation acc. to EN 60721-3-3
Degree of pollution according to EN 61800-5-1
Standards and Directives
Compliance with standards
CE marking
EMC Directive acc. to EN 61800-3 2004
Frame sizes FSA to FSF with integrated line
filter Class A
Frame sizes FSA to FSF with integrated or
external line filter Class B
Variable-speed electrical power drive systems –
Part 3: EMC product standard including specific
test methods
Electromagnetic compatibility – Part 3-12: Limit
values for temperature monitoring
UL approval for frame sizes FSD to FSF will be available soon.
Technical data
Conformity
Class 1K3
Temperature -25 to 55 °C (-13 to 131 °F)
Class 2K4
Temperature -40 to 70 °C (104 to 158 °F), max.
humidity 95 % at 40 °C (104 °F)
Class 3K3
Condensation, splashwater, and ice formation
not permitted
(EN 60204, Part 1)
Class 1C2
Class 2C2
Class 3C2
Class 1B1
Class 2B1
Class 3B1
2
UL, CE, c-tick
According to Low-Voltage Directive 2006/95/EC
With shielded motor cable up to 25 m:
Category C2, corresponds to Class A acc. to
EN 55011
Category C1, corresponds to Class B acc. to
EN 55011 for conducted interference emission
EN 61800-3: 2004
EN 61000-3-12: 2011 (RSCE > 250)
9
95 | 98
A5E36496664A_d
2016-03-17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents