6.6.3 Overview of parameters

Siemens
Building Technologies
p2267
120%
p2268
-20%
p2280
1
p2285
30s *
P2293
30s *
p2306
0
* The time settings, such as "Technology controller integral action time" are dependent on the used
frame size. For further information, refer to the Operating Instructions for the Control Unit
(A5E34257946A AB).
The recommended PID controller settings can be parameterized by means of a macro:
P0010 = 1
P0015 = 120 "PID settings for pumps or fans (only for optimization)"
P0010 = 0
Open the Parameters menu
Selection of the Parameters menu on BOP-2 and IOP-2
Table 11: Parameter selection
Overview of parameters
The table below contains only an excerpt from the parameter list. You can find a
complete list of parameters in List Manual CU230P (A5E02297932A AE).
Parameter
Factory
settings
p0601
0
p0730
r52.3
p0731
r52.7
p0732
r52.2
p0748
000
r0755[0..3]
-
Technology controller upper limit actual value
Technology controller lower limit actual value
Technology controller proportional gain
Technology controller integral time
Technology controller ramp-up/ramp-down time
Technology controller fault-signal inversion (heating or cooling)
Function
Motor temperature sensor type:
0: No sensor
1: PTC warning & timer
2: KTY84
4: Bimetallic NC contact warning & timer
6: Pt 1000
Digital output 0: Fault active
Digital output 1: Alarm active
Digital output 2: Operation enabled. Motor in operation.
Invert digital outputs (0 = do not invert, 1 = invert)
Bit 0: DO 0
Bit 1: DO 1
Bit 2: DO 2