4.1.15. Clock
A clock is available on the 50 series central units (see Figure 5-3).
Drift (typical) 4.3 min / month at 25 °C
The clock parameters are accessible:
Either in the following variables:
IW 62.08
seconds (0...59)
IW 62.09
minutes (0...59)
IW 62.10
hours (0...23)
IW 62.11
days of the week (1...7)
Monday = 1
IW 62.12
days of the month (1...depending on the month)
IW 62.13
months (1...12)
IW 62.14
years (00...99)
Or by using the UHR function
Updating the clock
The clock update can be effectuated in two ways:
Through the AC31GRAF software in the configuration window, by clicking on the "Set PLC
clock" icon (see Figure 5-4).
Through programming using the UHR function.
Here is an example using the UHR function:
%I62.00
%I62.01
%KW001.00
%KW001.01
%KW001.02
%KW001.03
%KW001.04
%KW001.05
%KW001.06
UHR
%M001.00
FREI
AKT
%MW001.00
S
FEHL
%MW000.00
SEC
ASEC
%MW000.01
MIN
AMIN
%MW000.02
H
AH
%MW000.03
TAG
ATAG
%MW000.04
MON
AMON
%MW000.05
JHR
AJHR
%MW000.06
WTG
AWTG
Page 5-23