7.2. ASCII/MODBUS
communication cables: 07 SK 51 and 07 SK 53
ABB Control - AC 31
1SBC 260400 R1001-b
06.99
Technical specifications
These cables allow you to connect the 40 or 50 series central units to other devices for ASCII
®
or MODBUS
communication.
They are shielded and 2 meters long.
7.2.1. 07 SK 51 connection diagram (see Figure 3-15):
Central unit end
MIN DIN 8
RxD
1
TxD
2
GND
7
5
8
3
6
4
Shield
PC end
SUB D9
3
TxD
(yellow)
2
RxD
(red)
5
GND
(black)
8
CTS
(white)
7
RTS
(blue)
1
CD
4
DTR
6
DSR
Shield