Detection:
LED status
- on the central unit:
- on the extensible
remote units :
- on the extensions:
- on non-extensible
remote units:
Reaction while powering
up or during central unit
usage:
Acknowledgment after
error removal:
ABB Control - AC 31
1SBC 260400 R1001-b
06.99
Diagnosis
A recapitulative table:
Class 1 errors:
Class 2 errors:
fatal errors
serious errors
Immediate
Immediate
ERR led on
ERR led on
RUN led off even if the
RUN led off even if the
RUN/STOP switch is on
RUN/STOP switch is on
RUN
RUN
All outputs remain on, or
All outputs remain on, or
are set to, 0.
are set to, 0.
The programming
The programming
software no longer has
software retains access
access to the central
to the central unit.
unit.
The user program has
The central unit remains
not started or is stopped.
on RESET while the
error remains present.
- Power on
- Power on
- Software cold restart
- Software warm start or
RESET
- Software
acknowledgment
Class 3 errors:
Class 4 errors:
light errors
warnings
- Bus error: if the central
- Unit error: the central unit
unit detects a frame
queries one slave per cycle.
control error (CRC) during
An error is detected
9 successive cycles
between 1 and 31 cycles.
or a timing error
- Program syntax error: The
or the absence of a reply
central unit detects this type
from a unit.
of error when passing from
- Cycle timing error: if the
STOP to RUN via the
switch
system detects the
overriding of the pre-
or via the software
defined cycle time after
or by on-line validation of a
16 consecutive cycles.
program modification.
ERR led on
ERR led on
According to the
Following a program syntax
configuration, the RUN
type error, the RUN led is
led is off even if the
off.
RUN/STOP switch is on
RUN
ERR led on or flashing
ERR led on
according to the case
Flashing SUPPLY led
Flashing SUPPLY led
Error led on or flashing
Error led on
according to the case
The inputs of a unit on
No program stoppage
error retain the old values
for 9 cycles and are then
reset to 0.
The outputs of a remote
unit or extension are reset
to 0.
No program stoppage by
default.
It's possible to prepare an
automatic program
stoppage with prior
configuration
(see chapter 5)
- Switch RUN/STOP from STOP to RUN
- Program launch through software
- Software warm restart
- Software cold restart
- Power on
- Software acknowledgment in the "STATUS" window"
- Acknowledgment through programming
- Test button on the 30 and 90 series remote units
- Automatic
acknowledgment if the error
code ≤ 15
Page 8-5

Hide quick links:

Advertisement

Table of Contents