4.4. Programming examples

Page 8-12
Diagnosis

4.4.1. Example of a reaction / command following a specific error

The following example enables commanding an alarm following an overload or short circuit on
the number 5 output of a ICMK 14 N1 remote unit with address 3 on the CS 31 bus. Another
output is also activated at the same time as the alarm in order to, for example, issue a cut the
actuators power command.
This is a class 4 type error and uses the following variables:
- M 255.14 : class 4 error presence bit
- MW 255.08 :
the error code
- MW 255.09 :
the unit type
- MW 255.10 :
the unit address
- MW 255.11 :
the defective channel number
%M255.14
%MW255.08
CODE_12
%MW255.09
TYPE_20
%MW255.10
ADD_3
%MW255.11
CHANNEL_5
&
=?
Z1=?
Z2
Q
=?
Z1=?
Z2
Q
=?
Z1=?
Z2
Q
=?
Z1=?
Z2
Q
ALARM
SHUT_DOWN
ABB Control - AC 31
1SBC 260400 R1001-b
06.99