5.5. Example of the output frequency monitoring

The following explains a program to read monitor functions of the inverter.
The following program reads the output frequency of station 1 inverter to D1.
Example : The output frequency of 50Hz is indicated 1388H (0.01Hz unit).
M9036
X0000 X000F X0001 X0020
Read
setting
M9036
X0000 X000F X0001
Please refer to "Section 4.4.6. Description of monitor code" about the details of a monitor code.
*When you refer to data by the monitor, be careful of a unit.

5.6. Example of the parameter writing

The following example program changes the f311 "Reverse-run prohibition selection"
setting of station 2 inverter to " 1 : Prohibit reverse run".
Reverse-run prohibition selection write code number : 2311H (Hexadecimal number)
Reverse-run prohibition set data
M9036
X0000 X000F X0001
M302
M303
M115
M9036
*To write parameters, add the triple figures that follow Fxxx to 2000H.
Example:
[ FROM H0000 H00E0 K4M100 K2]
[ TO H0000 H01E0 D100 K1]
M112
[ FROM H0000 H02E0 D1 K1]
[ TO H0000 H0160 K4M200 K2]
X0020
[ FROM H0000 H00E2 K4M100 K2]
X0020
Write setting
[ MOV H2311 D100]
[ MOV K0001 D101]
[ TO H0000 H01E6 D100 K2]
[ FROM H0000 H02E6 D2 K1]
[ TO H0000 H0162 K4M200 K2]
f311 -> 2311H
Reads the remote input (RX00 to RX1F)
data of buffer memory to M100 – M131.
[ MOV H0001 D100]
Sets the monitor code (01H) of the output
frequency to RWw0.
[ SET
M212]
Switches on the monitor command (RY1C).
Reads output frequency (RWr0) to D1
when monitoring (RX1C) switches on.
Writes M200 – M231 data to the remote
outputs (RY00 to RY1F) of buffer memory.
[ RST
M212]
Monitoring stop.
: 1 (Decimal number)
Reads the remote input (RX20 to RX3F)
data of buffer memory to M100 – M131.
[ PLS
M302]
[ SET
M303]
Writes F311 (2311H) to RWw6 and
setting data (1) to RWw7.
[ SET
M215]
Switches on the instruction code execution
request (RY2F).
Reads reply code (RWr6) to D2 when the instruction
code execution completion (RX2F) switches on.
[ RST
M215]
Switches of the instruction code execution
[ RST
M303]
request (RY2F).
Writes M200 - M231 data to the remote outputs
(RY20 to RY3F) of buffer memory.
24  −
− 