Unusual Diagnosis; Option Error; Disconnection Error Of Network Cable - Toshiba TOSVERT VF-AS1 Function Manual

Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

6. Unusual diagnosis

6.1. Option error

The error message is displayed when there is hardware error, software error or lose of
connection of wire.
Display of trip information
- 23 (Error code : 55) : Add-on option 1 error
e
(This error is displayed at the time the bottom side option has an error or only one option
is installed and has an error.)
- 24 (Error code : 56) : Add-on option 2 error
e
(This error is displayed at the time the two-units are installed and the upper side option
has an error.)

6.2. Disconnection error of network cable

■Display of trip information
err8 (Error code : 27) : Communication error
■Related parameter
『f850 Disconnection detection extended time』
『f851 Inverter operation at disconnection』
『 f852 Preset sped operation selection』
The range : 0.0 to 100.0 sec.
The waiting time from when a network error occurs to when a communication error
" err8 " is displayed can be adjusted. If a network error continues past the time set
in f850, it is recognized as a communication error and " err8 " is displayed.
When normal communication returns during the set time, a communication error is
not displayed and operation is continued.
The range 0 : Stop and Communication release
(CMOD, FMOD)
: None (continued operation)
1
: Deceleration stop
2
: Coast stop
3
: Network error (err8 trip)
4
: Preset speed operation (by f852 setting)
5
The action of the inverter when the communication error occurred can be specified.
Setting range
0
to 15 : Preset speed operation (by parameter setting)
1
: None
28  −
− 