Limitations - ABB 800xA User Manual

Multisystem integration
Hide thumbs Also See for 800xA:
Table of Contents

Advertisement

Limitations

Limitations
Export/Import
Export/Import is not possible to use with uploaded objects or structures since part of
the information for the proxy objects is stored in the Remote Access Client service.
Logical Colors
User defined logical colors used in graphic displays must be moved from the
provider to the subscriber by exporting and importing them.
Composite Graphic
Composite VBPG displays with references to instances in the control structure must
explicitly be uploaded to the control structure. If an old composite display resides
both in the functional structure and the control structure, the control structure should
be uploaded before the functional structure.
Aspect Link Control
Aspect link control dynamically programmed from Visual Basic can not be
uploaded from the provider and used in the subscriber system. Only use statically
configured aspect links.
Confirmed Write
Properties using confirm write is not supported by Multisystem Integration. OPC
properties using confirm write will be uploaded as read-only properties. Confirmed
write is used to write SIL-data to High Integrity (HI) controllers.
Object Lock
Object lock for systems with mixed AC800M controller and 800xA for Advant
Master controllers are supported. The only lock policy supported is Lock Optional
for Operation.
72
Section 3 Configuration
3BSE037076-510 D