Hitachi wj200 series Quick Reference Manual page 71

Hide thumbs Also See for wj200 series:
Table of Contents

Advertisement

Func.
Name
Code
b105
Free V/F setting,
voltage.3
b106
Free V/F setting,
freq.4
b107
Free V/F setting,
voltage.4
b108
Free V/F setting,
freq.5
b109
Free V/F setting,
voltage.5
b110
Free V/F setting,
freq.6
b111
Free V/F setting,
voltage.6
b112
Free V/F setting,
freq.7
b113
Free V/F setting,
voltage.7
B120
Brake control
enable
b121
Brake Wait Time
for Release
b122
Brake Wait Time
for Acceleration
b123
Brake Wait Time
for Stopping
b124
Brake Wait Time
for Confirmation
b125
Brake release
freq.
b126
Brake release
current
b127
Braking freq.
setting
B130
Deceleration
overvoltage
suppression
enable
B131
Decel. overvolt.
suppress level
b132
Decel. overvolt.
suppress const.
B133
Decel. overvolt.
suppress
proportional gain
"b" Function
Description
Set range, 0 to 800V
Set range, value of b104 to b108
Set range, 0 to 800V
Set range, value of b108 to b110
Set range, 0 to 800V
Set range, value of b108 to b112
Set range, 0 to 800V
Set range, b110 to 400(580)
Set range, 0 to 800V
Two option codes:
00...Disable
01...P012=00:Enable/
P012=02:Enable with DC breaking at
positioning end
02... P012=00:Enable/
P012=02:Enable without DC breaking at
positioning end
Set range: 0.00 to 5.00 sec
Set range: 0.00 to 5.00 sec
Set range: 0.00 to 5.00 sec
Set range: 0.00 to 5.00 sec
Set range: 0.00 to 400.0(580.0)
Set range: 0.00 to 200% of inverter rated
current
Set range: 0.00 to 400.0(580.0)
00...Disabled
01...Enabled
02...Enabled with accel.
DC bus voltage of suppression. Range is:
200V class...330 to 395
400V class...660 to 790
Accel. rate when b130=02.
Set range: 0.10 to 30.00 sec.
Proportional gain when b130=01. Range is:
0.00 to 5.00
71
*1
*1
Hz
*1
Hz
Defaults
A
B
Initial data
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
00
0.00
0.00
0.00
0.00
0.00
Rated
current
0.00
00
380
/760
1.00
0.20
Units
V
Hz
V
Hz
V
Hz
V
Hz
V
s
s
s
s
Hz
A
Hz
V
s

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents