Func.
Name
Code
C106
AM gain adjustment
C109
AM bias adjustment
C111
Overload warning level 2
C130
Output [11] on delay
C131
Output [11] off delay
C132
Output [12] on delay
C133
Output [12] off delay
C140
Relay output on delay
C141
Relay output off delay
C142
Logic output 1 operand A
C143
Logic output 1 operand B
C144
Logic output 1 operator
C145
Logic output 2 operand A
C146
Logic output 2 operand B
C147
Logic output 2 operator
C148
Logic output 3 operand A
C149
Logic output 3 operand B
C150
Logic output 3 operator
"C" Function
Description
Set range is 50. to 200.%
Set range is 0. to 100.%
Sets the overload warning signal level
between 0% and 200% (from 0 to two time
the rated current of the inverter)
Set range is 0.0 to 100.0 sec.
Set range is 0.0 to 100.0 sec.
Set range is 0.0 to 100.0 sec.
All the programmable functions available
for logic (discrete) outputs except LOG1 to
LOG3, OPO, no
Applies a logic function to calculate [LOG]
output state,
Three options:
00...[LOG] = A AND B
01...[LOG] = A OR B
02...[LOG] = A XOR B
All the programmable functions available
for logic (discrete) outputs except LOG1 to
LOG3, OPO, no
Applies a logic function to calculate [LOG]
output state,
Three options:
00...[LOG] = A AND B
01...[LOG] = A OR B
02...[LOG] = A XOR B
All the programmable functions available
for logic (discrete) outputs except LOG1 to
LOG3, OPO, no
Applies a logic function to calculate [LOG]
output state,
Three options:
00...[LOG] = A AND B
01...[LOG] = A OR B
02...[LOG] = A XOR B
78
Defaults
A
B
Initial
Units
data
100.
%
0.
%
Rated
current
A
x 1.15
0.0
s
0.0
s
0.0
s
0.0
s
0.0
s
0.0
s
00
00
00
00
00
00
00
00
00