Disruption
Monitoring not working
SMS message received in which there
are placeholders between 2 exclama-
tion points
6.4

Loading firmware

New firmware versions
If a new firmware version is available for the module, you will find this on the Internet pages
of Siemens Industry Online Support at:
Link: (https://support.industry.siemens.com/cs/ww/en/ps/15383/dl)
Save the firmware file on the configuration PC.
Downloading new firmware files
You load a new firmware file from the configuration PC on the CMR via the WBM.
You will find a description of establishing the connection to the CMR from the configuration
PC in the section Establishing a connection to the CMR (Page 63).
You will find a description of loading a firmware file via the WBM of the CMR in the section
Firmware (Page 79).
LOGO! CMR2020,
LOGO! CMR2040
Operating Instructions, 10/2016, C79000-G8976-C356-03
Meaning
Expected SMS messages config-
ured in the WBM are not received
A signal name specified in the WBM
does not exist or has been written
incorrectly. The incorrect or non-
existent signal name is then shown
in the message texts as follows:
[CMR_I1] becomes !CMR_I1!
Diagnostics and maintenance
6.4 Loading firmware
Solution
Check in the WBM:
Are the assignments active?
Are the inputs/outputs connected
correctly?
Only if objects of the BM are moni-
tored:
Is the BM connected?
Correct placeholders in theWBM
135