1. Hold down the SET button for 5 to 10 seconds.
The CMR shuts down to the safe status: All LED indicators are off.
2. Disconnect the CMR from the power supply.
You can also shut down the CMR to the safe status via the WBM.
The CMR can no longer be woken out of the shutdown status. To restart you need to turn
the power supply off and on again.
3.4

Commissioning the device

3.4.1

Steps in commissioning

To commission the CMR, follow the steps below:
Overview of commissioning
1. Note the requirements for operating the CMR, refer to the section Requirements for use
(Page 18).
2. SIM card: Before you insert the SIM card, note the information in Insert the SIM card and
enter the PIN (Page 44) regarding the two different methods:
– Method 1: For a new device
– Method 2: Replacing the SIM card in a device that has already been in use.
3. Connect a PC with a Web browser to the local interface X1P1 of the CMR, refer to the
section Establishing a connection to the CMR (Page 63).
4. Insert the SIM card, see section "Insert the SIM card and enter the PIN (Page 44)".
5. Connect the antennas.
6. Connect the CMR to the power supply.
7. Enter the PIN of the SIM card via the Web user interface of the CMR, refer to the section
Mobile wireless settings (Page 87).
8. Align the antenna, refer to the section "Wireless cell (Page 91)".
9. Set up the CMR according to your requirements, refer to the section Configuration (WBM)
(Page 53).
LOGO! CMR2020,
LOGO! CMR2040
Operating Instructions, 10/2016, C79000-G8976-C356-03