Loading to target system
You can use this function to load the current STARTER project to the Control Unit.
The data is loaded to the working memory of the Control Unit. A reset is then trig-
gered.
With the exception of the "Load project to target system" and active "Copy from
RAM to ROM" buttons, the data then has to be saved in a non-volatile memory
using the "Copy from RAM to ROM" function.
This function can be activated as follows:
S Right-click Drive unit –> Target system –> Load to target system
S Drive unit grayed out –> "Load to target system" button
S Project to all drives simultaneously:
"Load project to target system" button
Loading to PG
You can use this function to load the current Control Unit project to STARTER.
This function can be activated as follows:
S Right-click Drive unit –> Target system –> Load to PG
S Drive unit grayed out –> "Load to PG" button
Restoring the factory settings
You can use this function to set all the parameters in the working memory of the
Control Unit to the factory settings. To ensure that the data on the CompactFlash
card is also reset to the factory settings, choose the "Copy from RAM to ROM"
function.
For more information about STARTER, see Getting Started.
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Commissioning
Important STARTER functions
3-45