7.4.2
Communication detail settings
Make the settings according to the usage environment.
Item
Transmission Speed
Data Bit
Stop Bit
Parity
*1
Delay Time
GOT Station
32bit Storage
*1
The GOT ensures in advance the minimum interval (3.5 characters time) for communication frame defined in the MODBUS/RTU.
Therefore, the actual send delay time is as follows.
When connecting to MODBUS/RTU master equipment which requires a delay longer than 3.5 character time, adjust the send
delay time.
POINT
POINT
POINT
If the communication with MODBUS/RTU master equipment is not established, some equipment
which requires a delay longer than 3.5 character time may be connected.
Adjust the send delay time in the communication detail setting.
POINT
POINT
POINT
(1) Communication interface setting by the Utility
(2) Precedence in communication settings
Set this item when change the transmission speed used for communication
with the connected equipment.
(Default: 19200bps)
Set this item when change the data length used for communication with the
connected equipment.
(Default: 8bits)
Specify the stop bit length for communications.
(Default: 1bit)
Specify whether or not to perform a parity check, and how it is performed
during communication.
(Default: Even)
Set this item to adjust the transmission timing of the communication request
from the GOT.
(Default: 0ms)
Set the station No. of the GOT.
(Default: 1)
Select the steps to store two words (32-bit data).
(Default: LH Order)
Actual send
Send delay time set in the
=
delay time
communication detail setting
The communication interface setting can be changed on the Utility's [Communication setting]
after writing [Controller Setting] of project data.
For details on the Utility, refer to the following manual.
GOT2000 Series User's Manual (Utility)
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
Description
+
3.5 character time
Minimum interval for
communication frame
defined in MODBUS/RTU
7.4 GOT Side Settings
Range
9600bps,19200bps,38400bps,
57600bps,115200bps
7bit/8bit
1bit/2bit
None
Even
Odd
0 to 300ms
1 to 247
LH Order/HL Order
7 - 13