Setup Instructions

Notes:
• The following instructions apply when using the Hand Programmer.
• In PROGRAM mode, you can use the ARROW keys
parameter number.
• The default parameter values are indicated by an asterisk (*) in the tables.
Using the hand programmer, set each parameter value to suit your application. (For
detailed instructions on accessing a parameter and changing the value, see page18.)
1.
Select a language (P010:
Language)
If a language is selected, parameter
titles for parameters P010 to P001 are
displayed in the auxiliary reading field.
0
1
Values
2
3
4
2.
Select the measurement mode required for the application (P001:
Operation)
1
Values
2
3
To measure how full the vessel is, select Level: the reading can be returned as level or as
volume (or flow – seeP050 on page 32 for details):
for a level reading, ensure P050 is set to 0: the reading returns the distance from
process empty level (Empty) to the current level
for a volume reading, select a vessel shape at P050, and set volume parameters
051 to 055 as required
To measure how much space remains in the vessel, select Space:
Space returns a reading for the distance between current level and process full
level (Span)
To measure the distance from the transducer face to the current level, select Distance.
Page 20
SITRANS Probe LU – INSTRUCTION MANUAL
* Numeric/None
English
German
French
Spanish
Level returns material level referenced from Empty (process empty level).
*
The reading is returned in volumetric units if parameters 050 to 055 are
set to enable this.
Space returns material level referenced from Span (process full level).
Distance returns material level referenced from the transducer face.
to scroll to a
Parameter Auxiliary reading
P000
LOCK
P001
OPERATION
P002
MATERIAL
P003
MEAS RESP
P005
UNITS
P006
EMPTY
P007
SPAN
P010
LANGUAGE
7ML19985HT01