Got Ethernet Setting - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal microcomputers, modbus/fieldbus products, peripherals
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

Holding
Set the read points of the holding
registor read
register.
times
(Default: 125 points)
Set the read points of the input
Input register
register.
read times
(Default: 125 points)
Set the write points of the coil.
Coil write times
(Default: 800 points)
Holding
Set the write points of the holding
register write
register.
times
(Default: 100 points)
*1
Each of [GOT Station] set in the communication detail setting
and [Station] set in the Ethernet setting must be set to
different station numbers.
6.3.4 Ethernet setting
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
6.3.3
1 to 125 (points)
1 to 125 (points)
1 to 800(points)
1 to 100(points)
Item
GOT
IP Address
Subnet Mask
Default
Gateway
Peripheral S/W
Communicatio
n Port No.
Transparent
Port No.
6. MODBUS(R)/TCP CONNECTION

GOT Ethernet Setting

Description
Set the IP address of the GOT.
(Default: 192.168.0.18)
Set the subnet mask for the sub
network.(Only for connection via
router)
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
Set the router address of the
default gateway where the GOT is
connected.(Only for connection via
router)
(Default: 0.0.0.0)
Set the GOT port No. for the S/W
communication.
(Default: 5015)
Set the GOT port No. for the
transparent function.
(Default: 5014)
6.3 GOT Side Settings
6
Range
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013, and
49153)
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013, and
49153)
6 - 5