Other Settings - Mitsubishi Electric AE-200A Instruction Book

Control system/centralized controller
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

No.
Item
1
Device No.
2
Segmentation
APDU Segment
3
Timeout
4
APDU Timeout
5
APDU Retries
6
I-Am Timer
7
Vender ID

8-4-1-2. Other Settings

Sets 5 other settings items for the AE-200.
No.
1
Use Dry Mode
2
Use Fan Speed Mid1/Mid2
Not reflect communication error
3
to alarm signal
4
Use Operation Mode State Auto
5
Old Model Compatibility Mode
*1 Depending on the unit model, in addition to High/Low, this may have 2 extra fan speeds (Mid1/Mid2). Refer to the Instruction Book for
air conditioning unit for details of supported equipment. Fan speeds in this case are "High" > "Mid1" > "Mid2" > "Low".
WT07921X01
Set the AE-200 device number.
(Setting range: 0 to 4194302)
®
In BACnet
communications, segmentation applies to both
sending and receiving (fixed).
Set the monitoring time for segment responses to sent
segmented data.
(Setting range: 0 to 99999 msec)
Leave [5000] as it is unless otherwise specified.
Set the monitoring time for responses to sent data.
(Setting range: 0 to 99999 msec)
Leave [6000] as it is unless otherwise specified.
Set the number of send retries.
(Setting range: 0 to 99)
Leave [3] as it is unless otherwise specified.
Specify the AE-200 "I-Am" send period (units: seconds).
(If "0", only the initial "I-Am" is sent, with no subsequent
periodic sends.)
AE-200 vender ID appears.
(MITSUBISHI ELECTRIC AC&R: 99 (fixed))
Item
Check the checkbox to use an operation mode "Dry".
Check the checkbox to use fan speeds Mid1 and Mid2.
Check the checkbox NOT to reflect the communication
error status to an alarm signal (BI_01xx03).
Leave the checkbox unchecked unless otherwise specified.
Check the checkbox to display "Auto" whenever the
operation mode is set to "Auto".
Uncheck the checkbox to display the actual operation mode
(Heat or Cool).
The setting is only displayed when [Acquire Settings] is
performed and cannot be changed on the BACnet
Tool.
Description
Description
36
Default value
3
Both
5000 (msec)
6000 (msec)
3
0
99
Default setting
Unchecked
*1
Unchecked
Unchecked
Unchecked
®
Setting
Unchecked