Mitsubishi Electric AE-200A Instruction Book page 43

Control system/centralized controller
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

8-4-3-2. Notification Address
(1) Setting "Notification Address"
Sets the COV number notification destination device. Select the [COV No.] (left) for the device to set,
and under [Notification Address] (right), click [Add] to display the [Notification Address] pop-up window. A
maximum of 5 devices can be set for each COV No. (including broadcast).
No.
Item
Notification Address
1
Network No.
2
Device No.
3
Process Identifier
Notification Type
Unconfirmed/
4
Confirmed
WT07921X01
Sets the network number for the COV notification destination
device. Here, this is fixed to "Local".
Sets the device number for the COV notification destination device.
(Select from device numbers set in 8-4-2 "Network and Device".)
Sets the process ID for the COV notification destination address.
(Setting range: 0 to 4294967295)
Set to "0" unless otherwise specified.
Sets the type of the COV notification to send.
Unconfirmed: Unconfirmed COV Notification
Confirmed: Confirmed COV Notification
43
Description
Default
Local
Broadcast
(When IPv4 is used)
0
Unconfirmed