8-4-2-2. Device Address
Registers other devices such as central monitoring devices that send and receive data with the AE-200. A
maximum of 11 devices can be registered as communications devices (including broadcast).
(1) Registering communications device
Sets communications device information. Click [Add] to display the [Device Address] pop-up window.
No.
Item
1
Instance No.
2
Broadcast
3
IP Address
4
Port No.
WT07921X01
Check the radio button to set the device number.
Enter the device instance number.
(Setting range: 0 to 4194302)
Check the radio button to broadcast transmission.
Enter the IP address of the device.
®
The BACnet
port number of the device is displayed here.
Leave [47808] as it is unless otherwise specified.
40
Description
Default
Checked
(Blank)
Unchecked
192.168.2.x
47808