Section 11
Test the IED
11.6.9.2
80
Displays available instances of the function SXCBR with several measurements
per instance. Apart from apparatus position (POSITION), truck position
(TR_POS), operation counter (CNT_VAL), latest value of error indication
(L_CAUSE) and error indication during command (CAUSE) which have integer
values as outputs, the measurement values are boolean and provide status
information about processes and devices.
Circuit switch SXSWI
Main menu/Test/Function status/Control/Apparatus control/
CircuitSwitch(XSWI)/XS
Displays available instances of the function with several measurements per
instance. Apart from apparatus position indication (POSITION), the value of the
operation counter (CNT_VAL), the latest value of the error indication during
command (L_CAUSE) and error indication during command (CAUSE) which have
integer outputs, the measurement outputs have boolean values indicating the status
of processes and devices.
Bay reserve QCRSV
Main menu/Test/Function status/Control/Apparatus control/
BayReserve(CRSV)/CR
Displays available instances of the function QCRSV with several measurements
per instance. Apart from the measurement for exchange signals between different
BayRes blocks the output values are all boolean and indicate the status of processes
and devices.
Reservation input RESIN
Main menu/Test/Function status/Control/Apparatus control/ReservationInput/
RE
Displays available instances of the function RESIN with six measurements per
instance. Apart from the exchange measurement (EXCH_OUT), the measurement
outputs are all boolean and provide information about acknowledgements from
other bays, reservation requests form other bays (RE_RQ_B) and also validity
checks regarding requests (V_RE_RQ).
Bay control QCBAY
Main menu/Test/Function status/Control/ApparatusControl/BayControl/CB
Displays available instances of the function QCBAY with three measurements per
instance. The operator place allocation (PSTO) measurement has an integer as
output data, whereas the Update of position is blocked (UPD_BLKD) and Function
is blocked for commands (CMD_BLKD) have boolean output data.

Autorecloser SMBRREC

Main menu/Test/Function status/Control/AutoRecloser(RREC,79)/AR