1MRK 511 188-UEN C
11.6.11.3
11.6.11.4
11.6.11.5
11.6.11.6
11.6.11.7
11.6.11.8
Operator's manual

Tripping logic SMPPTRC

Main menu/Test/Function status/Logic/TripLogic(PTRC94)/TRP
Displays available instances of the function SMPPTRC with some measurements
per instance. The output data from each measurement is boolean and indicates the
existence of various trip signals. For example, if the output from parameter TRL1
is one, this indicates that a trip signal from phase L1 has been generated.

Trip matrix logic TMAGGIO

Main menu/Test/Function status/Logic/TripMatrix(GGIO)/TR
Displays available instances of the function TMAGGIO with some boolean output
values per instance. The output signals from this function block are typically
connected to other logic blocks or directly to IED output contacts.

Logic gate

Main menu/Test/Function status/Logic/LogicGate/GT
Displays available instances of the gate output. The output data type is an integer
with a possible value from 0 to 255.

Logic SR/RS memory

Main memory/Test/Function status/Logic/LogicSRMemory/SM
Displays available instances of the function SM. The output data presented in the
HMI is boolean and indicates whether or not a signal is present. For example, an
output of one from SM01 OUT indicates that a signal exists on that output.

Logic SR/RS Memory qt

Main memory/Test/Function status/Logic/LogicSRMemory_qt/SN
Main memory/Test/Function status/Logic/LogicRSMemory_qt/SN
Displays available instances of the function SM. The output data presented in the
HMI is boolean and indicates whether or not a signal is present. For example, an
output of one from SM01 OUT indicates that a signal exists on that output.

Logic timer set

Main menu/Test/Function status/Logic/LogicTimerSet/TS
Displays available instances of the function (TS). The output data type is boolean
and indicates whether the output from the timer pickup is delayed (ON) or if the
drop out (OFF) is delayed.
Section 11
Test the IED
85

Advertisement