Group 53: EFB PROTOCOL
This group defines set-up variables used for an embedded
fieldbus (EFB) communication protocol. Refer to the
communication protocol documentation for more information on
these parameters.
Code Description
5301 EFB PROTOCOL ID
Contains the identification and program revision of the protocol.
• Format: XXYY, where xx = protocol ID, and YY = program revision.
5302 EFB STATION ID
Defines the node address of the RS485 link.
• The node address on each unit must be unique.
5303 EFB BAUD RATE
Defines the communication speed of
the RS485 link in kbits per second (kb/s).
1.2 kb/s
2.4 kb/s
4.8 kb/s
9.6 kb/s
19.2 kb/s
38.4 kb/s
57.6 kb/s
76.8 kb/s
5304 EFB PARITY
Defines the data length parity and stop bits to be used with the RS485
link communication.
• The same settings must be used in all on-line stations.
0 = 8
1 – 8 data bits, no parity, one stop bit.
NONE
1 = 8
2 – 8 data bits, no parity, two stop bits.
NONE
2 = 8
1 – 8 data bits, even parity, one stop bit.
EVEN
3 = 8
1 – 8 data bits, odd parity, one stop bit.
ODD
5305 EFB CTRL PROFILE
Selects the communication profile used by the EFB protocol.
0 =
ABB DRV LIM
conforms to ABB Drives Profile, as used in ACS400.
1 =
DCU PROFILE
DCU Profile.
2 =
ABB DRV FULL
Drives Profile, as used in ACS600/800.
5306 EFB OK MESSAGES
Contains a count of valid messages received by the drive.
• During normal operation, this counter is increasing constantly.
298
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
– Operation of the Control Word and Status Word
– Operation of Control/Status Words conforms to 32-bit
– Operation of Control/Status Words conforms to ABB
Parameter listing and descriptions
ACH550-01 User's Manual
Range
0...0xFFFF
0...65535
1.2, 2.4, 4.8, 9.6, 19.2,
38.4, 57.6, 76.8 kb/s
0...3
0...2
0...65535

Hide quick links: