Figure 3-1
The following rules apply for external cable cross sections:
● Minimum PA cross section ≥ 10 mm
● The cable cross section of the central protective conductor is calculated from the cable
Line connection S (mm
S ≤ 16
16 ≤ S ≤ 35
S ≥ 35
Additional references
Configuration Manual, EMC Guidelines
3.1.3

RI suppression measures

In addition to the protective grounding of system components, special precautions must be
taken to ensure safe, fault-free operation of the system. These measures include shielded
signal lines, special equipotential bonding connections, and isolation and shielding
measures.
NCU
Manual, 03/2010, 6FC5397-0AP10-3BA0
Shielded signal line with reference ground
Motor
Encoder
Equipotential bonding conductor
Protective conductor
Grounding concept
cross section of the line connection as follows:
)
2
3.1 Secondary electrical conditions
2
Protective conductor SL min. (mm
S
16
S/2
Application Planning
)
2
21