Huawei R240D Hardware Installation page 56

Remote units
Hide thumbs Also See for R240D:
Table of Contents

Advertisement

R240D
Hardware Installation and Maintenance Guide
Issue 03 (2016-01-26)
Figure 5-45 Installed OT terminal
Install two OT terminals on a post.
Before you install two OT terminals on a post, ensure that the two terminals can be
installed on the post and that the electrical connecting pieces have a large contact area.
Two OT terminals can be installed using any of these methods:
Bend the upper OT terminal at a 45- or 90-degree angle, as shown in Figure 5-46.
Cross the two terminals, as shown in Figure 5-47.
Figure 5-46 Bending the upper OT terminal at a 45- or 90-degree angle
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.