Siemens SIMATIC S5 Manual page 150

Interface of the programmable controller
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

Data Transmission by Accessing Layer 2 Services
The procedures to follow for entering, modifying and transferring DB1 are described in detail in
section 1.4.
DB1 Parameters for Layer 2 Services
Parameter
Block ID: SL2:
STBS
STBR
Argument
Permiss. range
n
MBx
MBy
*
SAP 64 is the default SAP
**
The next flag is reserved as length flag.
Retentive flags are also overwritten with 00
Example: Two S5-95Us communicating with each other using layer 2 services.
DB1 PLC 1
156:
KS
='
168:
KS
=' BDR 500
180:
KS
='5120
192:
KS
='SDT 1 12
204:
KS
='STBS 48 MB77
216:
KS
='STBR 49 MB79
.
.
.
DB1 PLC 2
156:
KS
='
168:
KS
=' BDR 500
180:
KS
='5120
192:
KS
='SDT 1 12
204:
KS
='STBS 48 MB77
216:
KS
='STBR 48 MB79
.
.
.
Once you have assigned the parameters, you must develop the control program for data
communications. You will learn how to do this in the next section.
8-10
Table 8-3. Layer 2 Services, DB1 Parameters
Argument
n MBx
n MBy
33 to 54, 64
*
1 to 253
1 to 253
on a cold PLC restart.
H
Table 8-4.
Entering Parameters for Layer 2 Services
SL2: TLN 1
STA AKT';
HSA 10
TRT ';
SET 0
ST 400
';
SDT 2 360
';
';
';
SL2: TLN 2
STA AKT';
HSA 10
TRT ';
SET 0
ST 400
';
SDT 2 360
';
';
';
SAP number and location of the 'Send' status byte
SAP number and location of the 'Receive' status byte
Explanation
SAP number
Flag byte
Flag byte
Basic L2 parameters ( for description see 1.4)
Sending via SAP No. 48, 'Send' STB = FY 77;
Receiving via SAP No. 49,
'Receive' STB = FY 79
(FY 78 and 80 are reserved as length bytes)
Basic L2 parameters ( section 1.4)
Sending via SAP No. 48, 'Send' STB = FY 77;
Receiving via SAP No. 49,
'Receive' STB = FY 79
(FY 78 and 80 are reserved as length bytes)
S5-95U, SINEC L2
Meaning
SINEC L2
**
**
Explanation
EWA 4NEB 812 6112-02