Installation Guidelines
2.3
Linking Bus Segments with the L2 Repeater
2.3.1
Electrical Design of the SINEC L2 Repeater RS 485
Voltage Potentials for a Correct EMC Installation of the L2 Repeater
•
Bus segment 1 and bus segment 2 are electrically isolated from each other.
•
Bus segment 2 and the power supply have a common reference potential.
•
The reference potential (M terminal) and the protective ground conductor (PE terminal) are not
connected to one another.
•
All the shield clamps are connected to the protective ground conductor (PE terminal) at the
factory. The clamps for the power supply and bus segment 2 are connected internally to the
PE terminal. The connection between bus segment 1 and the PE terminal can be removed
(remove connecting plate between bus segments 1 and 2).
•
Terminal C ("C" stands for common) is not needed to connect the two-wire SINEC L2 bus
cable.
Expansion
interface
Connecting
plate
Shield clamp connected to PE
terminal via the connecting plate
Figure 2-5. Voltage Potentials for the SINEC L2 Repeater RS 485
Grounding Methods
Installation on a standard mounting rail
Installation on a metal plate of a cabinet or on a
wall
2-4
Power
Fault
Bussegment 1
Active
Fault
Bit rate
Bus terminated
Bus terminated
Bussegment 1
C
A
B A B C
Permanent internal connection
between shield clamp and PE
terminal
Siemens
SINEC L2
Bussegment 2
Active
Fault
Repeater
RS 485
Bussegment 2
PS 24V
C
A B A B C
M
Ground the standard mounting rail
Connect the protective ground clamp of the
repeater to the grounding rail using the
shortest cable possible (cross section
2
1.5 mm
, approximately AWG 16)
S5-95U, SINEC L2
Expansion
interface
L1+ M L2+ PE
Internal connection between M
terminal of the power supply and C
terminal of bus segment 2
EWA 4NEB 812 6112-02