DB1 Parameters, DB1 PAFE, TRT
Example of Calculating the Target Rotation Time
Four active and two passive stations are connected to the SINEC L2 network.
TLN of the active stations:
TLN of the passive stations:
HSA:
BDR:
SET:
ST:
SDT1:
SDT2:
Data traffic for
•
Station 1:
ZP master
PLC to PLC conn. SDA frame with 30 bytes of transmit data to station 2:
PLC to PLC conn. SDA frame with 30 bytes of transmit data to station 3;
PLC to PLC conn. SDA frame with 30 bytes of transmit data to station 4
•
Station 2:
PLC to PLC conn. SDA frame with 30 bytes of transmit data to station 1
•
Station 3:
PLC to PLC conn. SDA frame with 30 bytes of transmit data to station 1
•
Station 4:
PLC to PLC conn. SDA frame with 30 bytes of transmit data to station 1
Calculation of the basic frame load and the required time:
Token frames:
Station 1:
1·SRD with 6
1·SRD with 20 bytes of net data
3·SDA with 30 bytes of net data
Station 2:
1·SDA with 30 bytes of net data
Station 3:
1·SDA with 30 bytes of net data
Station 4:
1·SDA with 30 bytes of net data
Target rotation time to set:
Tip to optimize the target rotation time:
•
Assign the station addresses in ascending order (1, 2, ...).
A-6
1, 2, 3, and 4
40, 41
4
500 kBaud
0
400 bit time units
12 bit time units
360 bit time units
SRD frame with 4 bytes of transmit data to station 40:
2 bytes of received data from station 40;
SRD frame with 10 bytes of transmit data to station 41;
10 bytes of received data from station 41
4·145
bytes of net data
500+6·11
500+20·11
3·(425+30·11)
425+30·11
425+30·11
425+30·11
Sum (rounded up):
6400 bit time units ·
=
580
bit times units
=
566
bit times units
=
720
bit times units
= 2265
bit times units
=
755
bit times units
=
755
bit times units
=
755
bit times units
= 6400
bit times units
1
= 12800 µs
500 kBaud
EWA 4NEB 812 6112-02
S5-95U, SINEC L2