Peripheral devices

2.1.2
Peripheral devices
Check the model of the inverter you purchased. Appropriate peripheral devices must be selected ac-
cording to the capacity.
Refer to the table below to prepare appropriate peripheral devices.
200 V class
Motor
output
[kW]
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
Tab. 2-2:
Assumes the use of a Mitsubishi 4-pole standard motor with the power supply voltage of 200 V AC
50 Hz.
Select an MCCB according to the power supply capacity.
Install one MCCB per inverter.
For the use in the United States or Canada, provide the appropriate UL and cUL listed fuse or UL489
molded case circuit breaker (MCCB) that is suitable for branch circuit protection. (Refer to the
Installation Guideline.)
The magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic
contactor is 500,000 times. When the magnetic contactor is used for emergency stops during
motor driving, the electrical durability is 25 times.
If using an MC for emergency stop during motor driving, select an MC regarding the inverter input
side current as JEM1038-AC-3 class rated current. When using an MC on the inverter output side
for commercial-power supply operation switching using a general-purpose motor, select an MC
regarding the rated motor current as JEM1038-AC-3 class rated current.
2 - 4
Molded case circuit breaker (MCCB) or
Earth leakage circuit breaker (ELB)
Applicable inverter
model
Power factor improving (AC or DC)
FR-A820-00046(0.4K)
FR-A820-00077(0.75K)
FR-A820-00105(1.5K)
FR-A820-00167(2.2K)
FR-A820-00250(3.7K)
FR-A820-00340(5.5K)
FR-A820-00490(7.5K)
FR-A820-00630(11K)
FR-A820-00770(15K)
FR-A820-00930(18.5K)
FR-A820-01250(22K)
FR-A820-01540(30K)
FR-A820-01870(37K)
FR-A820-02330(45K)
FR-A820-03160(55K)
FR-A820-03800(75K)
FR-A820-04750(90K)
Breakers and contactors (200 V class)
MCCB
INV
MCCB
INV
(NF, NV type)
reactor
Without
With
5A
5A
10A
10A
15A
15A
20A
15A
30A
30A
50A
40A
60A
50A
75A
75A
125A
100A
150A
125A
175A
150A
225A
175A
250A
225A
300A
300A
400A
350A
400A
400A
Fig. 2-2:
M
Installation of the breakers
M
Installation and wiring
Input-side magnetic contactor
Power factor improving (AC or DC)
reactor
Without
With
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T21
S-T10
S-N25
S-T21
S-N25
S-N25
S-N35
S-N35
S-N50
S-N50
S-N65
S-N50
S-N80
S-N65
S-N95
S-N80
S-N150
S-N125
S-N180
S-N150
S-N220
S-N180
S-N300
S-N300
I002770E