Mitsubishi Electric MELSEC-Q Series Programming Manual page 178

Melsap-l
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Number
Name
SM320
SFC program
presence/absence
SM321
SFC program START/
STOP
SM322
SFC program START
status
SM323
All-blocks continuous
transition status
APPENDICES
176
Appendix 1 Special Relay and Special Register List
Meaning
Explanation
OFF: Not started
• Switched ON to begin the
(Watchdog timer reset)
step transition watchdog
ON: Started (Watchdog
timer count.
timer start)
• Watchdog timer is reset
when switched OFF.
OFF: SFC program not
• The same value as in
executed (stop)
SM320 is set as the
ON: SFC program
default value.
executed (start)
(Automatically switches
ON when the SFC
program exists.)
• When this relay is
switched from ON to OFF,
the SFC program
execution is stopped.
• When this relay is
switched from OFF to ON,
the SFC program
execution is restarted.
OFF: Initial START
The SFC program start
ON: Resumptive START
mode set in the SFC setting
of the PLC parameter dialog
box is set as the default
value.
At initial start: OFF
At resume start: ON
OFF: Continuous
Set whether a continuous
transition enabled
transition will be performed
ON: Continuous transition
or not for the block where
disabled
the "continuous transition
bit" of the SFC information
devices has not been set
Set by
Corresponding CPU
(When set)
(1)
(2)
S (Initial)
*1
S (Initial), U
S (Initial), U
U
(3)
(4)
(5)