8.16

DR 16 simulation value

8.16.1

Overview

Specifying a weight value using data record DR 16 disables the measuring input of the
SIWAREX module and "simulates" a weight with the specified value. The SIWAREX module
must first be released for simulation mode in DR 3 and then switched to simulation mode
with command no. 3.
Procedure
● Release simulation mode in DR 3
● Enter the weight to be simulated
● Transfer the data record to the SIWAREX module
● Start the simulation using command "Weight simulation on (3)"
● Stop the simulation using command "Weight simulation off (4)"
Table 8- 17
Assignment of data record 16
Variable
Note
Data record
Contains no. of data record
number
Length
Data record length information
Application
Information about which applica-
tion the data record belongs to
Version identi-
Information about current data
fier
record version
Weight simula-
Weight value specification (only
tion specifica-
relevant if simulation mode is
tion
enabled)
(Page 110)
Reserve 1
Reserve
Reserve 2
Reserve
8.16.2

Weight simulation specification

Only use weight simulation values which are within the measuring range of the scales. The
word "TEST" is displayed on the main display during simulation and a status bit is set. From
the start of simulation onward, all parameterized limits, inputs and outputs etc. refer to the
simulation weight.
SIWAREX WP231
Manual, 07/2014, A5E31238908A-02
Type
Length
Rw
(bytes)
USHORT
2
r
USHORT
2
r
USHORT
2
r
USHORT
2
r
FLOAT
4
rw
SHORT
2
rw
USHORT
2
rw
Scale parameters and functions
8.16 DR 16 simulation value
Default
Min.
Max.
16
-
-
16
-
-
101
-
-
1
1
65635
0
maxi-
maximum
mum
weighing
weigh-
range
ing
range
0
0
-
0
0
-
Modbus
registers
1592
1593
1594
1595
1596
1598
1599
109