Scale parameters and functions

8.17 DR 17 analog output control specifications

8.17
DR 17 analog output control specifications
8.17.1

Overview

If data record DR 17 is configured as the source for the analog output (see Analog output
source (Page 94)), specifying a control output sends a corresponding output current at the
analog output.
Procedure
● In data record DR 7, check that "Control by DR17" has been configured as the source for
the analog output
● Check the analog output configuration (see Analog output source (Page 94))
● Enter a value in data record DR 17
● Transfer the data record to the scales
Table 8- 18
Assignment of data record 17
Variable
Note
Data record
Contains no. of data record
number
Length
Data record length information
Application
Information about which application
the data record belongs to
Version identi-
Information about current data record
fier
version
Analog output
Value which is to be output (only
specification
relevant if source is "External specifi-
(Page 111)
cation", see DR 7)
Reserve 1
Reserve
Reserve 2
Reserve
8.17.2

Analog output specification

The value to be entered must be between the start value (Page 94) and the end value
(Page 94) of the analog output.
110
Type
Length
Rw
(bytes)
USHORT 2
r
USHORT 2
r
USHORT 2
r
USHORT 2
r
FLOAT
4
rw
SHORT
2
rw
USHORT 2
rw
Default
Min.
Max.
17
-
-
16
-
-
101
-
-
1
1
65635
0
-
-
0
0
-
0
0
-
Manual, 07/2014, A5E31238908A-02
Modbus
registers
1600
1601
1602
1603
1604
1606
1607
SIWAREX WP231