Dr 2 Command Code; Dr 3 Calibration Parameters; Overview - Siemens SIWAREX WP231 Manual

Hide thumbs Also See for SIWAREX WP231:
Table of Contents

Advertisement

Scale parameters and functions

8.2 DR 2 command code

8.2
DR 2 command code
DR 2 is a special data record used to transfer commands to the SIWAREX module by
SIWATOOL.
8.3

DR 3 calibration parameters

8.3.1

Overview

The calibration parameters need to be checked and if necessary modified for all scales.
The scale is basically defined by calibration parameters and calibration operation. A wire
jumper on the P-PR (Parameter Protection) terminals means that the DR 3 data can no
longer be changed (write-protected). All changes in data record 3 require service mode to be
switched on for the module. If service mode is not active, all parameter inputs are directly
rejected with an error.
Procedure
● Check all parameters and modify them as required
● Transfer the DR 3 data record from SIWATOOL to the scales
● Adjust the scales
● Transfer the DR 3 data record from the scales to SIWATOOL
Table 8- 1
Assignment of data record 3
Variable
Note
Data record
Contains no. of data record
number
Length
Data record length information
Application
Information on which application
the DR belongs to
Version
Information on the current data
identifier
record version
Scale name
Maximum length and actual
header
length of string for scale name
Scale name
Scale name specified by user
(Page 68)
Unit of
Maximum length and actual
weight head-
length of string for unit of weight
er
(e.g.: g, kg, t, ...)
Unit of
Unit of weight
weight
(Page 68)
64
Type
Length
Read/write
(bytes)
protection
USHORT
2
r
USHORT
2
r
USHORT
2
r
USHORT
2
r
UBYTE[2]
2
rwP
CHAR[12]
12
rwP
UBYTE[2]
2
rwP
CHAR[4]
4
rwP
Default
Min.
Max.
3
-
-
192
-
-
101
-
-
1
1
65635
12.12
-
-
" "
-
-
04.04
-
-
"kg••"
-
-
Manual, 07/2014, A5E31238908A-02
Modbus
registers
1000
1001
1002
1003
1004
1005
1011
1012
SIWAREX WP231

Advertisement

Table of Contents
loading

Table of Contents