ABB 2CSYK1102C/S Product Manual page 13

Switch actuator with rocker switches
Table of Contents

Advertisement

MYLOS
Building Automation
®
"Enable scene function (8 Bit)" parameter
The "8-Bit scene" object is enabled through this parameter.
Options:
- no
- yes
The scene parametrisation for the X output is implemented in the "X: Scene" parameter window, which is enabled
with the option "yes".
With "no" the parameter window will be locked and not visible.
Parameter "Enable logic function"
This parameter enables the "Logic".
Options:
- no
- yes
The parametrisation for the X output is implemented in the "X: Logic" parameter window, which is enabled with the
option "yes". The parameter window remains active when the setting is "no".
Forced operation switching status
Forced operation refers to the safety 1 bit or 2 bit "Forced operation" object of X output that is available for each output.
Options:
- inactive
- unchanged via 1 bit object
- ON via 1 bit object
- OFF via 1 bit object
- switching status via 2 bit object
With the option "inactive" the object "forced operation" is not visible and the forced operation function is not active.
The options "unchanged via 1 bit object", "ON, via 1 bit object" and "OFF, via 1 bit object" refer to the 1 bit "Forced
operation" safety object and determine the output switching status during forced operation.
A "Forced operation" 2 bit object is enabled with the option "switching status via 2 bit object". The telegram value
that is sent via the 2 bit object determines how it follows switch position:
Value
Bit 1 Bit 0 Access
0
0
0
Free
1
0
1
Free
2
1
0
OFF
forced
3
1
1
ON
forced
Commissioning
Description
If the "Forced operation" object receives a telegram with value "0" (00 binary) or "1"
(01 binary), the output is enabled and can be operated through different objects.
If the "forced operation" object receives a telegram with value "2" (10 binary) or
"1", the terminal output is switched off and remains disabled until forced operation
is deactivated again.
It is not possible to operate using another object as long as the forced operation
is active.
The output status can be programmed at the end of the forced operation.
If the "forced operation" object receives a telegram with value "3" (11 binary),
the terminal output is switched on and remains disabled until forced operation is
deactivated again.
It is not possible to operate using another object as long as the forced operation
is active.
The output status can be programmed at the end of the forced operation.
MYLOS
Building Automation | Commissioning 13
®

Advertisement

Table of Contents
loading

This manual is also suitable for:

2csyk1106c/s2csyk1103c/s

Table of Contents