Bit Scene Rocker Switch - ABB 2CSYK1102C/S Product Manual

Switch actuator with rocker switches
Table of Contents

Advertisement

MYLOS
Building Automation
®
3.1.6

8 bit scene rocker switch

No.
Function
16
Disabling
23
Disabling
The channel circuitry can be blocked or enabled using the communication object.
A blocked channel behaves as if there was no input signal. The communication
objects of the channel are still available.
17
8 bit scene
24
8 bit scene
This communication object sends the following values over the bus to fulfil the scene setting.
1-Byte value [ON/OFF]
22
Store scene
29
Store scene
This communication object appears only with the option "object value = 1".
This option can be set in the parameter "Store scene". This communication object is used to start scene storage
over the bus.
The function depends on the type of scene storage.
34
Disabling LED
35
Disabling LED
The "Disabling Led" communication object makes it possible to enable (1) the LED so as that it switches
on or off depending on the operating mode selected from the parameters or to disable it (0) forcing it into a
continuous switching off status.
Operation of communication objects
Object name
Rocker switch 1
Rocker switch 2
Rocker switch 1
Rocker switch 2
EIS 1
Rocker switch 1
Rocker switch 2
Rocker switch 1
Rocker switch 2
MYLOS
Type of datum
1 bit DPT_Enable
1 bit DPT_Enable
1 byte DPT_Unsigned_
Counter_value
1 byte DPT_Unsigned_
Counter_value
DPT 1.001 switching command
1 bit DPT_Enable
1 bit DPT_Enable
1 bit DPT_Enable
1 bit DPT_Enable
Building Automation | Operation of communication objects 39
®
Flags
C,W
C,W
C,W,T,U
C,W,T,U
C,W,T,U
C,W,T,U
C,W
C,W

Advertisement

Table of Contents
loading

This manual is also suitable for:

2csyk1106c/s2csyk1103c/s

Table of Contents